Offshore Commissioning Support in Brazil
In March 2025, our service team was deployed to provide offshore commissioning support in Brazil for 10 units of heaters and control panels, the largest having a capacity of 720 kW.We received reports of high temperatures on the heaters. Upon investigation, we discovered that insulation jackets were improperly installed on the heaters' flanges at the stand-off area. This insulation trapped heat, resulting in elevated temperatures on the heater flanges. It is essential that the heater flanges and stand-off areas remain uninsulated to allow accurate readings of flange temperatures, particularly for T-class